Media · source heat · heat pump

Source heat: the lower, the better.

Buildings are better insulated every year and need less heat. Less heat means lower water temperature. And low water temperature is where a heat pump works most efficiently. The future lies where the source water drops almost to room temperature.

35/30°CWinter · flow/return water
18/21°CSummer · flow/return water, dew-point controlled
≤ 29°CFloor surface · EN 1264 comfort limit
~1,8timesheat pump efficiency at 35 °C compared with 70 °C

Chain of causation

Four links, one result.

01INSULATION

The envelope improves

Walls, roofs and windows let less heat escape.

02DEMAND

The heat load falls

Less heating power is needed per square metre.

03TEMPERATURE

The water cools

A large radiant surface gives the same comfort with low water temperature.

04COP

Efficiency rises

The heat pump moves more heat with less electricity.

Data evidence · 1970–2010

Source temperature has approached floor temperature.

In radiator systems, boiler water fell only from 90 °C to 70 °C in forty years. In underfloor heating (ISIYER), over the same period it fell from 60 °C to 30 °C: the water temperature became almost equal to the floor temperature.

  • Radiator: small surface, high temperature required
  • Underfloor heating: large surface, low temperature is enough
  • The floor surface stays below the 29 °C comfort limit
RadiatorISIYER · underfloor heating29 °C floor limit
100 75 50 25 0 Boiler water · °C 90609050 70407030 1970199020002010
Source: PEXa / ISIYER field archive · typical design values

Cross-check · the Carnot limit

Why low temperature? That is what physics says.

The theoretical maximum efficiency of a heat pump depends on how high it “pumps” the heat. The lower the target temperature, the more heat is moved with the same electricity.

COP=Thot÷(Thot − Tcold)
Flow waterSystemCarnot COPRealistic COP*
70 °COld radiator4,9≈ 2.2
55 °CNew radiator6,0≈ 2.7
45 °CFan coil / low-temperature radiator7,1≈ 3.2
35 °CISIYER · Bioiklim8,8≈ 4.0

* Assuming outdoor air at 0 °C (273.15 K); real devices reach about 45% of the Carnot limit. Result: a heat pump running at 35 °C uses about 1.8 times less electricity for the same heat than one running at 70 °C.

Q outdoor airQ floorW electricity EvaporatorCondenserCompressorExpansion valve low pressurehigh pressureQ floor = Q outdoor air + W electricity
Heat pump cycle · winter mode · schematic

The most important device · the heat pump

It does not produce heat, it moves it.

A heat pump collects heat from the outdoor air with a refrigerant, raises its temperature with a compressor and releases it into the floor. The electricity used is only part of the heat moved. In summer the same device reverses the cycle and moves the home’s heat outside.

Winter · heating35/30 °C

Flow/return water; floor surface ≤ 29 °C

Summer · cooling18/21 °C

Flow/return water; a dew-point sensor prevents condensation

Dew-point control

A humidity sensor continuously measures the dew point in the room. The water temperature never drops below this value, so no condensation forms on the ceiling or floor.